Check the Bottom Joint in a Fire-Rated Wall

A one- or two-hour wall needs the right protection where it meets the floor. Check the wall design and bottom-joint system together before installation.

Waterguard Blog2 min read
Wall and joint

Read both designs.

The wall design identifies the framing, gypsum layers and other parts of the wall. The joint system identifies the materials and arrangement at the wall-to-floor connection.

UL’s guidance explains that components from different rated systems are not automatically interchangeable. Use the complete joint system that fits the wall and floor.

Check the adopted code and project requirements to determine the joint protection required. Drywall clearance alone does not define a universal joint width or firestop detail.

Test standards

Wall tests and joint tests answer different questions.

UL 263 and ASTM E119 cover fire-resistance testing of building assemblies. UL 2079 and ASTM E1966 cover fire-resistive joint systems.

For a joint product, review the complete listing and installation requirements. A wall’s hourly rating does not identify the material or dimensions required at the bottom joint.

Waterguard FS

What UL BW-S-0078 covers.

UL BW-S-0078 lists Waterguard FS as the fill, void or cavity material for 1- and 2-hour joints under ANSI/UL 2079. The joint rating equals the wall rating. The listing also includes Canadian ratings under CAN/ULC S115.

Use ⅝-inch gypsum board: one layer for one-hour walls and two layers for two-hour walls. BW-S-0078 references U300, V300, W300, U400, V400 and W400 Series wall designs, subject to the listing’s additional requirements.

The listing covers qualifying reinforced-concrete, UL Classified hollow-core precast, and D700 or D900 fluted-steel floor-unit/concrete assemblies. Check the complete listing for the floor thickness, wall framing, fastening and dimensions.

The U.S. L Rating is less than 1 CFM per linear foot at ambient temperature and 400°F. Sound performance comes from separate acoustic wall tests.

Installation

Check these four details.

Snap FS onto the outermost board layer on both sides of the wall before hanging. Face the shorter leg outward and keep the intumescent strip in contact with the floor.

Use this checklist with the complete listing. Each dimension refers to a different part of the installation.

  1. 01Board thickness5/8-inch gypsum board, with the layer count required by the specified one-hour or two-hour construction.
  2. 02Bottom jointNominal 3/4-inch bottom-of-wall joint.
  3. 03Floor contactNo gap between the FS profile and the floor; the intumescent material contacts the floor.
  4. 04Section jointsMaximum 1/8-inch gap between adjoining Waterguard FS sections.
Before hanging

Give the crew the wall design and joint detail.

Include the wall design and BW-S-0078 in the submittal and installation documents. Check the product, floor, framing, board layers, profile orientation and joints between sections before work starts.

BW-S-0078 uses FS without a separate bottom sealant application. If the proposed construction differs from the listing, get the design team’s direction before installing it.

Choose your product

Choose the right Waterguard for your wall.

½-inch profile · Non-fire-rated

Waterguard

Protects the drywall edge, supports rubber base and provides sound performance up to STC 71.

View Waterguard
1- and 2-hour fire-rated walls · BW-S-0078

Waterguard FS

Pink FS protects 1- and 2-hour joints under UL BW-S-0078 without a separate bottom sealant application. FS also achieves STC up to 71 in separate sound tests.

View Waterguard FS
1¾-inch profile · Non-fire-rated

Waterguard Plus

The taller profile provides over an inch of vertical water protection, rubber-base backing, smoke control and STC up to 57.

View Waterguard Plus

Follow the installation instructions for your product. For fire-rated walls, use Waterguard FS and the complete UL BW-S-0078 system.

Technical help

Request a BW-S-0078 project review.

Get specification assistance